Thermostat with pipeline or ambient temperature measurement -5°C / +15°C - RAYCHEM AT-TS-13
Thermostat with pipeline or ambient temperature measurement -5°C / +15°C - RAYCHEM AT-TS-13
nVent RAYCHEM AT-TS-13 pipeline thermostat with temperature control in the range of -5°C to +15°C. The set includes an NTC temperature sensor on a 3-meter-long cable, which can be shortened when measuring ambient temperature. The wire of the temperature sensor can be extended up to 100 m using a two-wire cable with a conductor cross-section of 1.5 mm2. If the sensor cables are laid in cable routes or near high voltage lines, the extension cables should be shielded. The cable shield should be grounded only on the controller side.
- The temperature setting can be checked through a window located in the case age.
- The thermostat has three LEDs to indicate the operating status.
- Green light - the heating cable power on.
- Red light - a break in the sensor circuit.
- Red light - a short circuit in the sensor circuit.
Technische gegevens
Catalogusnummer
728129-000
Meetnauwkeurigheid
± 1 K bij 5°C (kalibratiepunt)
Schakelhysterese
0,6 tot 1 K
Maximale bedrijfstemperatuur
+40°C
Relais
SPST (normaal open)
Stroomvoorziening
230 V WISSELSTROOM
Minimale bedrijfstemperatuur
-20°C
Certificeringen en goedkeuringen
CE
EN 60730-1
EN 60730-2-9
Terminals
Schroef 2,5 mm²
Huisvesting
Temperatuurverandering
In de koffer
Bedrijfstemperatuur
-20°C / +50°C
Beschermingsgraad
IP 65
Gaten voor wartels
1 x M20 voor voedingskabel (Ø 8-13 mm)
1 x M25 voor verwarmingskabel (Ø 11-17 mm)
1 x M16 voor sensor
Materiaal
ABS
LED-indicatoren
Inclusief verwarmingskabel (groen)
Sensorcircuitonderbreking (rood)
Kortsluiting in het sensorcircuit (rood)
Sensor
Type
PTC KTY 83-110
Max. thermische weerstand van de sensorkabel
80°C
Materiaal sensorkabel
PVC
Diameter sensor
6,5 mm
Draaddiameter
5,5 mm
Lengte van verwarmingskabel
3 m