Thermostat with pipeline or ambient temperature measurement -5°C / +15°C - RAYCHEM AT-TS-13
Thermostat with pipeline or ambient temperature measurement -5°C / +15°C - RAYCHEM AT-TS-13
nVent RAYCHEM AT-TS-13 pipeline thermostat with temperature control in the range of -5°C to +15°C. The set includes an NTC temperature sensor on a 3-meter-long cable, which can be shortened when measuring ambient temperature. The wire of the temperature sensor can be extended up to 100 m using a two-wire cable with a conductor cross-section of 1.5 mm2. If the sensor cables are laid in cable routes or near high voltage lines, the extension cables should be shielded. The cable shield should be grounded only on the controller side.
- The temperature setting can be checked through a window located in the case age.
- The thermostat has three LEDs to indicate the operating status.
- Green light - the heating cable power on.
- Red light - a break in the sensor circuit.
- Red light - a short circuit in the sensor circuit.
Technical data
Catalog number
728129-000
Measurement accuracy
± 1 K at 5°C (calibration point)
Switching hysteresis
0.6 to 1 K
Maximum operating temperature
+40°C
Relay
SPST (normally open)
Power supply
230 V AC
Minimum operating temperature
-20°C
Certifications and approvals
CE
EN 60730-1
EN 60730-2-9
Terminals
Screw 2.5 mm²
Housing
Temperature change
Inside the case
Operating temperature
-20°C / +50°C
Degree of protection
IP 65
Holes for cable glands
1 x M20 for power cable (Ø 8-13 mm)
1 x M25 for heating cable (Ø 11-17 mm)
1 x M16 for the sensor
Material
ABS
LED indicators
Attached heating cable power supply (green)
Break in the sensor circuit (red)
Short circuit in the sensor circuit (red)
Sensor
Type
PTC KTY 83-110
Maks. thermal resistance of the sensor cable
80°C
Sensor cable material
PVC
Sensor diameter
6.5 mm
Wire diameter
5.5 mm
Length of heating cable
3 m