Free delivery from 11,59 €
RAYCHEM AT-TS-14 - Thermostat with pipeline or ambient temperature measurement 0°C to +120°C (648945-000)
RAYCHEM AT-TS-14 - Thermostat with pipeline or ambient temperature measurement 0°C to +120°C (648945-000)
RAYCHEM AT-TS-14 - Thermostat with pipeline or ambient temperature measurement 0°C to +120°C (648945-000)
RAYCHEM AT-TS-14 - Thermostat with pipeline or ambient temperature measurement 0°C to +120°C (648945-000)
RAYCHEM AT-TS-14 - Thermostat with pipeline or ambient temperature measurement 0°C to +120°C (648945-000)
RAYCHEM AT-TS-14 - Thermostat with pipeline or ambient temperature measurement 0°C to +120°C (648945-000)
RAYCHEM AT-TS-14 - Thermostat with pipeline or ambient temperature measurement 0°C to +120°C (648945-000)
RAYCHEM AT-TS-14 - Thermostat with pipeline or ambient temperature measurement 0°C to +120°C (648945-000)

RAYCHEM AT-TS-14 - Thermostat with pipeline or ambient temperature measurement 0°C to +120°C (648945-000)

Temperature setting range0°C / +120°C
Relay output16 A
Catalog number648945-000
231,63 €
incl. VAT / pcs.
Lowest price in 30 days before discount: / pcs.
Regular price: / pcs.
14 days for easy returns
Safe shopping

RAYCHEM AT-TS-14 - an advanced thermostat designed specifically for temperature control in pipelines, with control over a wide range from 0°C to +120°C. This thermostat is ideal for precise temperature management in various industrial and commercial applications. It comes with an NTC temperature sensor on a 3-meter cable that can be shortened for ambient temperature measurement, providing flexibility and adaptation to specific installation requirements.

RAYCHEM The AT-TS-14 allows the sensor cable to be extended up to 100 meters using a 1.5 mm² twin-core cable, allowing installation in large systems and hard-to-reach locations. For reliable operation in harsh environments, sensor cables that are laid in cable routes or near high-voltage lines should be shielded and the shield grounded only on the controller side.

Choose RAYCHEM AT-TS-14 for reliable temperature control in pipelines, ensuring system efficiency and safety in any situation.

  • The temperature setting can be checked through a window located in the age of the housing.
  • The thermostat has three LEDs indicating the operation status.
    • Green light - power supply to the heating cable is on.
    • Red light - a break in the sensor circuit.
    • Red light - short circuit in the sensor circuit.
Brand
Symbol
AT-TS-14
Producer code
5017455006469
Warranty
Technical data
Catalog number
648945-000
Measurement accuracy
± 1 K at 5°C (calibration point)
Switching hysteresis
0.6 to 1 K
Maximum operating temperature
+40°C
Relay
SPST (normally open)
Power supply
230 V AC
Minimum operating temperature
-20°C
Certifications and approvals
CE
EN 60730-1
EN 60730-2-9
Terminals
Screw 2.5 mm²
Housing
Temperature change
Inside the case
Operating temperature
-20°C / +50°C
Degree of protection
IP 65
Holes for cable glands
1 x M20 for power cable (Ø 8-13 mm)
1 x M25 for heating cable (Ø 11-17 mm)
1 x M16 for the sensor
Material
ABS
LED indicators
Attached heating cable power supply (green)
Break in the sensor circuit (red)
Short circuit in the sensor circuit (red)
Sensor
Type
PTC KTY 83-110
Maks. thermal resistance of the sensor cable
80°C
Sensor cable material
PVC
Sensor diameter
6.5 mm
Wire diameter
5.5 mm
Length of heating cable
3 m